TROUBLESHOOTING HEAT PUMP SYSTEMS…TEST YOUR KNOWLEDGE

..OK, try this one. Heat pump system (R22) operating in cool cycle. Indoor coil fed by a TXV . Measured suction pressure is 50 psi, superheat is 12F. What’s wrong, most likely, with the system?

3 Responses to “TROUBLESHOOTING HEAT PUMP SYSTEMS…TEST YOUR KNOWLEDGE”

  1. sounds to me the system is having a problem with low evap air flow

  2. wayneshirley Says:

    ..yep, I would agree.

  3. Low sat. press. + Low superheat=Low air flow OR T-Stat set too low and space temp. very low